|
GLOSSARY
ANSI – American National Standards
Institute. An independent administrator and coordinator of voluntary
industry standards.
bypass
– A device which shunts current around the socket, so the meter
can be removed without interrupting service.
clearance – There are two, quite
different meanings for "clearance." One meaning is: A specified minimum
distance between two objects to assure adequate space for safety,
security, or access. The other meaning is: An agreement between a foreman
and the system operator, for permission. When describing new electric
services, "clearance" has the first meaning – the distance between
two objects.
common ground
point – The point where the grounding electrode connects to the
equipment-grounding conductor and/or the circuit-grounding
conductor.
conduit
– A pipe with a smooth interior surface for easy drawing-in of
electrical conductors. Conduit may be metallic or
nonmetallic.
corrosion
inhibiter – An electrical joint compound used to retard
oxidation at electrical connections.
current transformer – A
transformer whose secondary current is a precise fraction of its primary
current. Using current transformers, high-current circuits can be measured
with conventional meters. Abbreviation: CT.
demand – The average rate at which
energy (kilowatt hours) is consumed during a specified interval of time.
direct-burial cable
– Cable which may be installed in the ground without the
protection of a conduit.
direct-connect meter – A meter
which carries full load current and connects across full line voltage.
Also called a self-contained meter.
drip loop – A downward loop in the
customer's conductors, near where the customer's conductors attach to the
power company's overhead conductors, to prevent water from entering the
service mast at the weatherhead.
fault – A partial or total failure
of insulation which causes a short circuit between conductors, or between
a conductor and ground, causing an abnormal current to flow. Also, a
failure (break) in a conductor which causes an open circuit.
fault current – A
current which flows between conductors, or between a conductor and ground,
due to an abnormal connection between the two. A fault current flowing to
ground may be called a ground fault current.
guy – A cable or
brace that supports a mast or pole.
high leg – In a four-wire delta
service, the phase with a voltage higher than the other two phases. Also
called wild leg, delta leg.
instrument transformer – A
transformer which delivers as its output, a precise fraction of the input
line current or line voltage. Instrument transformers allow standard
meters to measure high currents and voltages.
instrument-rated meter – A meter
used in conjunction with instrument transformers, to measure high-voltage
or high-current services. Also called a transformer-rated
meter.
line conductor –
A service conductor installed by the electric utility, to the
meter.
load conductor –
A service conductor to the customer's load, after the
meter.
manual link bypass –
Provision for manually installing conductive links between the
line and load terminals in the meter socket. These links maintain
electrical service to the customer when the meter is removed. Also called
manual circuit-closing block.
manufactured home – A
factory-assembled structure built on a permanent chassis, transportable in
one or more sections, and designed to be used as a dwelling with a
permanent foundation. Also called a modular home. New electric service to
a manufactured home has the same requirements as installing new service to
a permanent single-family residence.
meter jaw – A spring-loaded
receptacle inside a meter socket which captures the terminals (blades) of
a meter, and connects the meter terminals to the service
conductors.
meter pedestal
– A factory-built assembly containing a meter socket and
disconnect switches.
meter
ring – A metal ring which secures the meter to the meter
socket, which can be sealed by the electric utility to prevent tampering
with the meter.
meter socket
– The mounting device consisting of meter jaws, connectors, and
enclosure for receiving a socket-type meter.
mobile home – A factory-assembled
structure built on a permanent chassis, transportable in one or more
sections, and designed to be used as a dwelling without a permanent
foundation. Overhead service to a mobile home is provided by a meter pole.
Underground service to a mobile home is provided by a meter pedestal.
NEC – National
Electrical Code. National regulations for the installation of electrical
equipment inside buildings. Published by the National Fire Protection
Association. NEC rules apply to equipment on the customer's side of the
point of delivery.
NEMA –
National Electrical Manufacturers Association. A trade
association which publishes standards for manufacturers of electrical
equipment, including enclosures and racks.
NESC – National Electrical Safety
Code. National regulations for the installation, operation, and
maintenance of electric supply and communication lines. Published by
Institute of Electrical and Electronics Engineers. NESC rules apply to
equipment on the electric utility's side of the point of delivery.
neutral – The
grounded conductor in a single-phase three-wire, or three-phase four-wire
system. point of
attachment – The point at which the utility's service
conductors are mechanically attached to the customer's premises. For
overhead services, the point of attachment is usually an insulated clevis.
point of delivery –
The point where the utility's service line makes the electrical
connection to the customer's wires. For overhead services, the point of
delivery is the splice between the utility's and the customer's
conductors. For underground services, the point of delivery is the
secondary lugs of the distribution transformer, or the service stubout, or
the secondary hand hole – if the utility's existing service is on the
customer's property. If the utility's existing service is not on the
customer's property, the point of delivery is the customer's property
line. The utility determines the point of delivery based, in part, on
convenient access to existing service.
power factor – Technically, the
cosine of the phase angle between the circuit voltage and current
waveforms. Since phase angles are difficult to measure, power factor is
usually derived by measuring power or impedance. Power factor is the ratio
of active power to apparent power (watts divided by volt-amperes). Power
factor has no units, but is commonly expressed as a percentage. For
example, if active power is 96 kW and apparent power is 100 kW, the power
factor is 96%.
primary
voltage – The voltage at which electricity is delivered from
substations to distribution transformers. Primary voltage is greater than
600 volts.
raceway
– An enclosed channel for holding wires or cables. If designated for line
conductors, the raceway must be sealable. The intermixing of line and load
conductors in the same raceway is not permitted.
seal – A locking device to secure
a meter or other service equipment.
secondary voltage – The voltage at
which electricity is delivered from distribution transformers to
customers. Secondary voltage is less than 600 volts.
select backfill – Soil or sand
free from sharp objects, rocks, scrap building material, and corrosive
material.
self-contained
meter – A meter which carries full load current and connects
directly across full line voltage. Also called a direct-connect
meter.
service drop –
For overhead service, the power company's service line between
the distribution transformer and the point of delivery.
service line – Conductors from the
distribution transformer to the customer's point of delivery. See service
drop, service lateral.
service entrance equipment – The
service equipment which is supplied by the customer: conduit, conductors,
mast, weatherhead, meter base, enclosures, disconnects, and
panels.
service
lateral – For underground service, the service line between the
distribution transformer and the point of delivery.
service mast – For overhead
service, the conduit rising above the meter to provide mechanical
protection to the customer's conductors and to support the service drop
from the power company.
socket – The mounting device for
socket meters. Includes spring-loaded meter jaws, connectors for line and
load conductors, and an enclosure.
temporary service – Electric
service during the construction phase of a project.
test switch – A device used to
isolate connections to a meter from its instrument transformers.
transformer-rated meter
– A meter used in conjunction with instrument transformers, to
measure high-voltage or high-current services. Also called an
instrument-rated meter.
UL
– Underwriters Laboratories. An independent product-testing and
certification organization.
voltage transformer – A
transformer whose secondary voltage is a precise fraction of its primary
voltage. Using voltage transformers, high-voltage circuits can be measured
with conventional meters. Abbreviation: VT, or PT (potential
transformer).
|