CURRENT TRANSFORMER
CABINET
The
customer provides and installs a cabinet for the current transformers, and
the conduit between the CT cabinet and the meter enclosure. The CT cabinet
is metal, weather tight, NEMA 3R rated, and securely mounted on a rigid
surface plumb in both directions. The cabinet is to have a side-hinged,
sealable door. When open, the door must not block a safe exit.
The
top of the cabinet must be no higher than 7 feet above the floor, and the
bottom of the cabinet must be at least 6 inches above the floor. The
dimensions of the CT cabinet are:
----------------------------------------------------------------------------------------------------------
Number
Cabinet
Service
of CTs Width
Height Depth
----------------------------------------------------------------------------------------------------------
Single-phase,
400-800 amps 2
30" 48"
11"
Three phase, 200-800 amps
3
36''
48'' 11''
Over 800 amps
Requires switchboard metering
----------------------------------------------------------------------------------------------------------
The
location of the CT cabinet is subject to the approval of the power
company.
Inside the cabinet, the customer installs a mounting base
for the CTs. A single-phase mounting base is used if the service is
single-phase, a three-phase mounting base is used if the service is
three-phase. The base has two cable termination bolts on the line and the
load side of each phase, and two bolts on the neutral bus.
The CT
cabinet contains only the main service conductors. A maximum of four main
service conductors may be served from the load side of each termination
bolt, as long as the lugs are not stacked and do not restrict mounting the
CTs. Use "stair step" lugs if more than two conductors are terminated at a
CT.
If
the CT cabinet is installed in a vehicle traffic area, install a guard
post.
Meter
Socket, Enclosure, and Conduit
The
distance between the meter socket enclosure and the CT cabinet is not less
than 10 inches and not more than 50 feet. Mount the two enclosures as
close together as feasible.
Meter
Socket and Enclosure for Single-Phase Circuits
For single-phase
circuits, the customer provides and installs a 6-terminal meter socket in
an enclosure, with conduit between the meter enclosure and the CT cabinet.

Meter
Socket and Enclosure for Three-Phase Circuits
For
three-phase circuits, the customer provides and installs a 13-terminal
meter socket in an enclosure, with conduit between the meter enclosure and
the CT cabinet

Conduit
For
conduit, use rigid steel, rigid PVC plastic (Schedules 40 or 80), or
IMC/EMT conduit. Flex conduit is not permitted. When metallic conduit is
used, provide grounding bushings at each end. When PVC conduit is used,
install a green insulated bonding jumper in the conduit. 1-1/4-inch
conduit or larger is required, with proper fittings and bushings to
protect metering conductors.
The conduit enters the meter
enclosure adjacent to the test switch.
A
pull cord is required if the conduit is over 25 feet. Conduit bends must
not exceed 360 degrees total.