SWITCHBOARD
METERING
A
custom-built switchboard is required for services over 800 amperes.
Switchboard metering may also be used on 201-800 amp services, at the
customer's option.
The switchboard will include the switchboard
service section, current transformer (CT) mounting base, meter socket,
provisions for a test switch, and means for locking the meter enclosure
with independent access by the power company. The customer must submit one
set of drawings to the power company for approval, prior to shipment of
the switchboard from the manufacturer.
The point of delivery must
be no more than 5 feet vertical or horizontal inside the building from the
point of entrance. Locate the metering compartment on the supply side of
the main switch or breaker, with the CTs in a CT compartment. The meter
socket and test switch may be mounted on the CT compartment's hinged
cover, or located remotely. The space below this compartment's barrier may
be used as the main switch (breaker) compartment, or a load distribution
compartment, or a bottom-fed terminating pull section.
The power
company will own, provide, and install the meter and test
switch.
CTs
may be installed either by the customer or the power company. The power
company is responsible for the wiring between the CTs and the meter.
Mount
each socket on the switchboard, or remotely, and connect it to the
switchboard with approved conduit.
6-Terminal
socket for single-phase services
13-Terminal
socket for three-phase services
Switchboard Meter Installation
A
typical switchboard meter installation is shown below, with three options
for locating the meter:
▪
Remotely mounted
▪ Flush with the panel
▪ Surface-mounted on the face of the
panel
