|
TRANSFORMER
INSTALLATIONS
The
power company is responsible for installing a padmount or submersible
(totally underground) transformer at the customer's site. Conductors to
the primary side of the transformer enter at the left side of the
transformer; conductors to the secondary side enter at the right. The
trench runs from the right side of the transformer to the customer's
building.
The customer is responsible for installing the service
conductors in the trench, from the transformer to the
building.
Safety Clearances Around
Transformers Clearances from padmount transformers to structures
are measured from the nearest metal portion of the transformer, to the
structure or any overhang.
The clearance from a building is 3 feet
if the building has non-combustible walls (brick, concrete, steel, or
stone), 10 feet if the building has combustible walls (including
stucco).
Other
clearances are shown on the next page. These clearances also apply to any
oil-filled electrical equipment.

Work Clearances Around Transformers A
minimum clearance of 10 feet of clear, level working space is required in
front of a padmount transformer, to allow use of hot sticks. Other
clearances are shown below for padmount transformers and for underground t
ransformers. These clearances apply to any oil-filled electrical
equipment.
Landscaping
and other obstructions must not encroach on these
clearances.


For
more information:
Guard
Posts |